INDUSTRIAL ELECTRICAL EQUIPMENTS

Product Range

  • Air Circuit Breaker Panels
  • Automatic Power Factor Improvement Systems
  • Cable Trays
  • Changeover Panels
  • Double Busbar Panels
  • Electrical Insulation Enhancement Systems
  • Electrical Safety Products
  • Feeder Pillars
  • High Tension Panels
  • Insulators and Surge-Power transformersArrestors
  • Motor Control Centers
  • PLC and Drive Panels
  • Power cables and accessories
  • Power Control Centers
  • Power Distribution Panels
  • Power transformers
  • Relay and Metering Panels


  • Power Control Centers are used for distribution and control ofvarious power source used in the industry. These power controlcenters control, monitor & continuously provide supply toconnected loads through breakers. If anything goes wrong withthe source or load, these PCCs comprising breakers cut downsupply and the rest of the system stays healthy. Normally PowerControl Centers are installed near the power source hence faultlevel is high. It is designed to suit the fault level of 50KA or 65 KAfor 1 sec. Busbar systems in Power Control Centers are designedto suit the fault level as well as temperature rise to 40°c aboveambient. Ample space is provided for cable termination. Variousprotections viz short circuit, overload, earth fault, under voltageetc. are provided to protect source and equipment.


    PCC - Specifications
    Type Fixed/Draw out fully componential, dust and vermin proof
    Protection class IP42 /IP 54/IP 55 - Optional
    Material of construction CRCA 10/12 /14/ 16 Gauge as required. Modular construction with a wide choice of compartment size
    Rated voltage 600 V, 50 HZ, 3 phase, 4wire
    Rated current Up to 6000A main busbar
    Short circuit level STD 50 KA 1 sec, optional 65 KA 1 sec
    Busbar support SMC / DMC
    Busbar Aluminum / Copper, Electrolytic grade
    Design standard IS 8623.DT
    Bus chamber With safety barrier
    Cable chamber Ample space for cabling with supports
    Entry Top or Bottom


    The primary electricity load in any industry arises from low and high voltagemotors. These motors being an integral part of any operation must be kept healthythroughout their lifetime. The Motor Control Centre takes care of controlling,monitoring & recording of the power supplied to motorsMCCs are suitable for operation of motors ranging from 0.5 HP to 500 HPcapacities. They can handle various types of starting methods including Directonline (DOL), Star-Delta, autotransformer, Soft starter etc. They can also beoperated locally or remotely using PCC(Power Control Center) and DCS(Distributed Control Center) systems. Enhanced thermal management in theMMCs is ensured for higher motor power ratings with the help of increased airventilation. The component layout is made so as to facilitate the ease of operationand maintenance.


    MCC - Specifications
    Type Modular /non-modular, Fixed/Draw out, single front/double front, dust and Vermin proof
    Protection class IP42 /IP 54/IP 55 - Optional
    Material of construction CRCA 12/14/16 gauge as per required. Interchangeability of compartment
    Rated voltage 380 / 415 / 440 V, 50 HZ, 3 phase, 4 wire
    Rated current 3200 A main bus bar
    Short circuit level 35 KA/50 KA for 1 sec
    Enclosure type Indoor/ outdoor
    Busbar support SMC/DMC, Epoxy
    Busbar Aluminum / Copper, Electrolytic grade
    Design standard IS 8623
    Bus chamber With safety barrier
    Cable chamber Ample space for cabling with supports
    Entry Top or Bottom


    Power Distribution Panel is a component of an electricity supply system thatdivides an electrical power feed into subsidiary circuits while providing aprotective fuse or circuit breaker for each circuit in a common enclosure. Sinceit is located downstream, the fault level is normally lower, which is in the rangeof 20 to 35 KA. Normally they are designed to carry currents up to 800 A. Theadvantage of using PDAs is to clear fault locally, without affecting theupstream switchgear.


    Features
    Single phase or three phase
    Split load and split metering
    MCB, RCBO, fuse distribution boards
    Complete with controls i.e. photocells, timers etc.
    Contactor controls
    Metering (with comm’s, Ofgem/MID approval, split load)
    Cable extensions
    Surge protection

    PDP - Specifications
    Type Fixed floor-mounted/ Wall-mounted ACB or MCCB.
    Protection class IP42 /IP 54/IP 55 - Optional
    Material of construction CRCA 12/14/16 gauge as per required. Interchangeability of compartment
    Rated voltage 440/ 415 V 50 Hz
    Rated current 800/ 600 A.
    Short circuit level 35/50 KA
    Enclosure type Indoor/ outdoor
    Busbar support SMC/DMC
    Busbar Aluminum / Copper, Electrolytic grade
    Design standard IS 8623
    Bus chamber With safety barrier
    Cable chamber Ample space for cabling with supports
    Entry Top or Bottom


    Air Circuit Breaker Panels are normally used for the protection of power source andelectrical equipment situated on the downstream. They isolate and protect the sourcefrom short circuit, overload, earth fault, under-voltage, etc.

  • Ratings: 400A to 6300A
  • Breaking Capacities: 50kA to 100kA
  • 3 Pole / 4 Pole Versions with Fix / Draw-out configuration
  • High Short time withstand capacity, Icu=Ics=Icw for 1 sec for total selectivity
  • Different terminal orientations: Flat, Horizontal and Vertical




  • HT Panels are used for the operation of potential transformers, capacitors and motors.They house HT Circuit Breakers, relays & metering that is used to receive 11KV/33KVsupply (from one or more source) and distribute the power through its outgoingfeeders. The outgoing feeder may be one or more it depends on the load.

    Main functions of HT panels

  • To make & break HT supply (or switch on or switch off supply),
  • To receive & distribute HT supply,
  • To provide protection against faults,
  • To provide metering to monitor various parameters.


  • Automatic Power Factor Control Panel is designed to maintain the power factor of the plantto unity. To maintain the power factor of unity means to achieve demand in KVA on thelower side. Power factor is maintained to set the value using APFC relay in auto modewhereas in case of failure of APFC relay pushbuttons are used. Auto, as well as the manualmode, is provided for power factor control. Various types of capacitors are used dependingon load conditions. Typically MPP, APP or mix dielectric types of capacitors are used. In caseof non-linear loads like VFD, UPS thyristor switching, suitable reactors are used along withcapacitors to filter harmonics.


    Type Automatic power factor correction panel
    APFC Relay Current sensing, KVAR sensing.
    Capacitor APP/MPP Heavy Duty/ Mix dielectric
    Type Higher size of contact rating for better performance on capacitor switching.
    Ventilation Exhaust Fan of adogvate capacitor with levels.
    Operation Auto operation through APFC controller and manual through PBS Time lag function is provided between the switching of capacitor
    Entry Top or bottom


    A feeder pillar is a cabinet used to house electrical equipment. Feederpillars act as a central circuit that controls and distributes electricity tooutgoing circuits downstream to the feeder pillar. This setup provides eachcircuit protection, along with the capacity to be easily controlled.A feeder pillar-box protects personnel from coming into contact with livewires, as well as protecting wires from dust and dampness.



    Ladder Cable Tray- Galvanized

    Channel Cable Tray- Galvanized

    Channel Cable Tray- Pultruded FRP







    How Can I Help You?